smart line E SLE 130 – 300 IMPORTANT! DO NOT UNDER ANY CIRCUMSTANCES SWITCH ON THE IMMERSION HEATER BEFORE THE PRIMARY TANK IS FILLED.
TECHNICAL AND INSTALLATION 6Immersion Heater The SmartLineE range of tanks have the facility for fitting a 3kW immersion heater for back-up emergenc
TECHNICAL AND INSTALLATION 74. COMMISSIONING Characteristics: Maximum water supply pressure to the reducing valve 16 Bar Operating pressure
TECHNICAL AND INSTALLATION 85. MAINTENANCE ACV recommend that the cylinder is maintained by a competent person, this should be carried out every 12
TECHNICAL AND INSTALLATION 96. TECHNICAL DATA Type SLE 130 SLE 160 SLE 210 SLE 240 SLE 300 Code 06604801 06604901 06605001 06605101 0660520
TECHNICAL AND INSTALLATION 10 7. PERFORMANCE Performances Type Peak output (l/10min) 1st hour output (ltrs/60min) Continuous output (ltrs/hr) Boi
TECHNICAL AND INSTALLATION 118. SYSTEM SCHEMATICS Typical un-vented application. Typical open vented application.
TECHNICAL AND INSTALLATION 12Typical ‘S-Plan’ schematic. ACV 6 PIN SOCKETFACTORY WIREDN IS SWITCHED LIVENOT NEUTRALCONTROL TERMINAL NUMBERING MAY DIF
TECHNICAL AND INSTALLATION 13Typical ‘Y-Plan’ schematic. ACV 6 PIN SOCKETFACTORY WIREDN IS SWITCHED LIVENOT NEUTRALCONTROL TERMINAL NUMBERING MAY DI
TECHNICAL AND INSTALLATION 149. DISCHARGE PIPE The discharge pipe (D2) from the tundish should terminate in a safe place where there is no risk to p
TECHNICAL AND INSTALLATION 15Extract from ‘The Building Regulations 1991 G3’
TECHNICAL AND INSTALLATION 1610. PARTS LIST Description Code 300mm Immersion Heater 11/2" BSP 3KW OI300 Thermostat pocket 438027 Manual air v
INDEX INTRODUCTION 1 Intended users of these instructions 1 Warnings 1 1. Operation 2 2. Construction 3 3. Installa
TECHNICAL AND INSTALLATION 1 INTRODUCTION Intended users of these instructions: - The specifying engineer. - The installation engineer. - The owne
TECHNICAL AND INSTALLATION 2 1. OPERATION A = Stainless steel internal tankB = STW 22 carbon steel exterior tankC = High density polyurethane foam
TECHNICAL AND INSTALLATION 3 2. CONSTRUCTION Internal tank: This tank is the heart of the assembly; it has to withstand the corrosive nature of
TECHNICAL AND INSTALLATION 43. INSTALLATION (130 to 300 Smart Paks) Domestic: 1. Connect 22mm x 3/4" FI BSP adaptors to cold water inlet (blue
TECHNICAL AND INSTALLATION 5Wiring the thermostat: To comply with ‘The Building Regulation 1991 G3.6’ the manual reset high limit thermostat must be